🏠 Home → Equipment → DRY CONTACT RELAY
The ROSSMA IIOT-AMS DRY CONTACT RELAY meter-switch is designed for remote control of high-voltage industrial equipment (up to 30 kW) using commands received via LoRaWAN or NB-IoT wireless networks.
The device is equipped with a powerful relay output (switching up to 240V 10A) and four discrete inputs for monitoring equipment status and pulse counting.

Fig. ROSSMA IIOT-AMS DRY CONTACT RELAY meter-switch appearance
Equipment is registered in the register of the Ministry of Industry and Trade of the Russian Federation as equipment manufactured on the territory of the Russian Federation (Conclusion 48859/11 dated June 11, 2021).
IMPORTANT: For switching inductive loads (motors, transformers), it is recommended to use an RC circuit (snubber) to protect relay contacts from arcing.
For high-power loads (>10 A): Use an intermediate contactor. The switch relay controls the contactor coil, which switches the power load (up to 30 kW).
The ROSSMA IIOT-AMS DRY CONTACT RELAY meter-switch has the following indicators:
The meter-switch has a RESET button for device restart.
Option 1: Direct load connection (up to 10 A)
┌────────────────────┐
220V ────┤ ROSSMA DRY CONTACT │
│ RELAY │
L ─────┤ L (phase) │
│ │
N ─────┤ N (neutral) │
│ │
PE ─────┤ PE (ground) │
│ │
│ RELAY OUT: │
│ COM ──────┬───────┼──── Load (lamp, pump, <10A)
│ │ │
│ NO ───────┘ │
└────────────────────┘
└──── Neutral (N)
Option 2: Connection via contactor (for high-power loads >10 A, up to 30 kW)
┌────────────────────┐ ┌───────────────┐
220V ────┤ ROSSMA DRY CONTACT │ │ Contactor │
│ RELAY │ │ (30 kW) │
L ─────┤ L (phase) │ │ │
│ │ ┌────┤ A1 (coil) │
N ─────┤ N (neutral) │ │ │ │
│ │ │ ┌──┤ A2 (coil) │
PE ─────┤ PE (ground) │ │ │ │ │
│ │ │ │ │ Power │
│ RELAY OUT: │ │ │ │ contacts: │
│ COM ──────────────┼────┘ │ │ │
│ │ │ │ L ───── L1 ─┼──── High-power
│ NO ───────────────┼──────┘ │ │ load
└────────────────────┘ │ N ───── N ─┼──── (up to 30 kW)
│ │
│ PE ───── PE ─┼────
└───────────────┘
Recommendation: For controlling powerful electric motors (>3 kW), use a magnetic starter or contactor with appropriate power rating.
| Terminal | Function | Description |
|---|---|---|
| L | Phase 230V | AC mains power |
| N | Neutral 230V | Neutral wire |
| PE | Ground | Protective grounding |
| COM | Relay output (common) | Common relay contact |
| NO | Relay output (normally open) | Closes when relay activates |
| IN1+ | Discrete input 1 (isolated) | Positive terminal |
| IN1- | Discrete input 1 (isolated) | Negative terminal |
| IN2+ | Discrete input 2 (isolated) | Positive terminal |
| IN2- | Discrete input 2 (isolated) | Negative terminal |
| IN3 | Discrete input 3 | Input (closes to GND) |
| IN4 | Discrete input 4 | Input (closes to GND) |
| GND | Common wire | Ground for IN3, IN4 inputs |
| +5V | External device power | +5V DC output (up to 500 mA) |